Depending on the type of valve, TA FM systems serially cover the torque range up to 700 Nm. NK FM systems are used when higher torques are required (up to 12,000 Nm) or the valve requires a faster motorized positioning time (<10s/90°).
TA FM systems in an explosion-proof version can be used in temperature class T3, e.g. for heating oil, and in explosion group 2C, e.g. for hydrogen. The magnetic coupling of the TA FM system has an encapsulation (mb).
TA FM systems do not require the gearbox of the electric drive to move to the safety position. The failsafe function can therefore also be triggered if the drive or gearbox is defective.
NK FM systems are delivered as AC drives with frequency converters. This enables the motor function to be optimized and torque changes in the valve to be detected.