Skip to content
Telephone availability: Mon - Thu 8 a.m. - 5 p.m., Fri 8 a.m. - 3 p.m.

TA safety valves

Opening on the suction or pressure side to protect the system

Plant protectionTA safety valves

We advise you

If you have a question about this or other products, just give us a call or send us a message using our contact form.

Question about this product?

Product description

The TA safety valves are often advertised as: “Renovation of elevated tanks” or “Safety valve for ventilation systems” or “Safety valve as additional over/underpressure protection to protect the structure in the event of operational disruptions”.

Downloads

TA 170 – 1 safety valve

Dimensions: ∅ 210 mm, height 210 mm Stricter requirements for the sterility of pure water mean that pure water containers must be hermetically sealed and ventilated using an air filter system. If built-in filters and control devices fail, the TA safety valve reduces the negative or positive pressure from large-volume, closed water basins when a certain pressure is reached by opening the suction or pressure side. The valve then closes automatically and the system remains ready for operation. Optionally, the safety valve can be equipped with inductive proximity switches to indicate a response in the control room. The response pressure is set at the factory and is stated on the nameplate. The TA safety valve is made of high-quality aluminum and coated on the outside in red RAL 3000.

  • Maximum building protection
  • Securing the air filter system
  • Absolutely maintenance-free
TypeTA 170-1Type 170 – 1 (108)TA 170-1 S*Type
Nominal diameter and pipe connectionDN 100 / ∅110DN 100 / ∅108DN 100 / ∅108 or 110Nominal size and pipe diameter
Air output at max Δ600 Nm3/H600 Nm3/H580 Nm3/HAir capacity on max Δ
response pressure50-1000 Pa50-1000 Pa50-1000 PaResponse pressure
Weight3.7 kg3.7 kg4.0 kgweight

*with fault alarm switch

TA 81 – 180 safety valve

Dimensions: ∅ 395 mm, height 595 mm Stricter requirements for the sterility of pure water mean that pure water containers must be hermetically sealed and ventilated using an air filter system. If built-in filters and control devices fail, the TA safety valve reduces the negative or positive pressure from large-volume, closed water basins when a certain pressure is reached by opening the suction or pressure side. The valve then closes automatically and the system remains ready for operation. Optionally, the safety valve can be equipped with inductive proximity switches to indicate a response in the control room. The response pressure is set at the factory and is stated on the nameplate. The TA safety valve is made of high-quality aluminum and coated on the outside in red RAL 3000.

  • Maximum building protection
  • Securing the air filter system
  • Absolutely maintenance-free
TypeTA 81 – 180 – ETA 81 – 180 – ES*TA 81 – 180**Type
Nominal diameter and pipe connectionDN 250 / PN 6DN 250 / PN 6DN 250 / PN 6Nominal size and pipe diameter
Air output at max Δ3100 Nm3/H2850 Nm3/H2100 Nm3/HAir capacity on max Δ
response pressure400 – 1600 Pa400 – 1600 Pa600 – 1500 PaResponse pressure
Weight32 kg34 kg48 kgweight

*with fault signaling switch **with fault signaling switch, trigger ball and viewing window

Downloads

In this download area you will find further details about the specifications of this product. If you have any questions about the product variants, options or customization options,

Back To Top