TA safety valves

Opening on the suction or pressure side to protect the system

Plant protectionTA safety valves

We advise you

If you have a question about this or other products, just give us a call or send us a message using our contact form.

Question about this product?

Product description

The TA safety valves are often advertised as: “Renovation of elevated tanks” or “Safety valve for ventilation systems” or “Safety valve as additional over/underpressure protection to protect the structure in the event of operational disruptions”.

Downloads

TA 170 – 1 safety valve

Dimensions: ∅ 210 mm, height 210 mm Stricter requirements for the sterility of pure water mean that pure water containers must be hermetically sealed and ventilated using an air filter system. If built-in filters and control devices fail, the TA safety valve reduces the negative or positive pressure from large-volume, closed water basins when a certain pressure is reached by opening the suction or pressure side. The valve then closes automatically and the system remains ready for operation. Optionally, the safety valve can be equipped with inductive proximity switches to indicate a response in the control room. The response pressure is set at the factory and is stated on the nameplate. The TA safety valve is made of high-quality aluminum and coated on the outside in red RAL 3000.

  • Maximum building protection
  • Securing the air filter system
  • Absolutely maintenance-free
Type TA 170-1 Type 170 – 1 (108) TA 170-1 S* Type
Nominal diameter and pipe connection DN 100 / ∅110 DN 100 / ∅108 DN 100 / ∅108 or 110 Nominal size and pipe diameter
Air output at max Δ 600 Nm3/H 600 Nm3/H 580 Nm3/H Air capacity on max Δ
response pressure 50-1000 Pa 50-1000 Pa 50-1000 Pa Response pressure
Weight 3.7 kg 3.7 kg 4.0 kg weight

*with fault alarm switch

TA 81 – 180 safety valve

Dimensions: ∅ 395 mm, height 595 mm Stricter requirements for the sterility of pure water mean that pure water containers must be hermetically sealed and ventilated using an air filter system. If built-in filters and control devices fail, the TA safety valve reduces the negative or positive pressure from large-volume, closed water basins when a certain pressure is reached by opening the suction or pressure side. The valve then closes automatically and the system remains ready for operation. Optionally, the safety valve can be equipped with inductive proximity switches to indicate a response in the control room. The response pressure is set at the factory and is stated on the nameplate. The TA safety valve is made of high-quality aluminum and coated on the outside in red RAL 3000.

  • Maximum building protection
  • Securing the air filter system
  • Absolutely maintenance-free
Type TA 81 – 180 – E TA 81 – 180 – ES* TA 81 – 180** Type
Nominal diameter and pipe connection DN 250 / PN 6 DN 250 / PN 6 DN 250 / PN 6 Nominal size and pipe diameter
Air output at max Δ 3100 Nm3/H 2850 Nm3/H 2100 Nm3/H Air capacity on max Δ
response pressure 400 – 1600 Pa 400 – 1600 Pa 600 – 1500 Pa Response pressure
Weight 32 kg 34 kg 48 kg weight

*with fault signaling switch **with fault signaling switch, trigger ball and viewing window